Horstmann C-Stat ZW Installationsanleitung Seite 3

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 16
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 2
3
Electrical Connections
WARNING: ISOLATE THE MAINS SUPPLY BEFORE
COMMENCING INSTALLATION
As the C-Stat is a wireless product with no electrical connections
all electrical wiring will be made to the ASR-ZW receiver.
All necessary electrical connections should now be made. Flush
wiring can enter from the rear through the aperture in the
backplate.
The mains supply terminals are intended to be connected to the
supply by means of fixed wiring.
The receiver is mains powered and requires a 3 Amp fused spur.
The recommended cable size is 1.0mm².
The receiver is double insulated and does not require an earth
connection, an earth connection block is provided on the
backplate for terminating any cable earth conductors. Earth
continuity must be maintained and all bare earth conductors
must be sleeved. Ensure that no conductors are left protruding
outside the central space enclosed by the backplate.
1 2 3 4LN
Internal
Electronics
230V 50Hz COMM OFF ON
ASR-ZW Receiver internal wiring diagram
The receiver has Voltage Free contacts. A link between Live and
terminal 2 is required for mains Voltage applications.
Seitenansicht 2
1 2 3 4 5 6 7 8 ... 15 16

Kommentare zu diesen Handbüchern

Keine Kommentare